Enphase Resources
The Manufacturer Resource Articles document the most common issues and difficulties when entering a particular manufacturer's equipment into SolarAPP+. If you see an issue that is not documented or needs improvement/ changes. Please reach out to [email protected]
https://enphase.com/download/nec-2017-2020-and-2023-enphase-system-code-compliance
Great Resource to find any Enphase Data Sheet.
Commonly Used Spec Sheets. And SA+ Examples
5P-1P-NA Spec Sheet Battery Weight 174 LBs Round-Up.
Common Errors
GETTING STARTED WITH ENPHASE MICRO INVERTERS
https://enphase.com/installers/training/getting-started/install
IQ7 LINKS
IQ 7 / IQ 7+ Field Wiring Diagram - Support | Enphase
https://enphase.com/download/iq7-iq7-microinverter-data-sheet
https://enphase.com/sites/default/files/2021-11/IQ7-series-MC4-Micro-Manual-EN-US.pdf
IQ8 LINKS
https://enphase.com/download/iq8-series-microinverter-installation-and-operation-manual
https://enphase.com/download/iq8-series-microinverter-installation-guide
https://enphase.com/download/iq8-and-iq8-microinverters-data-sheet
IQ8M & IQ8A Spec Sheet
https://enphase.com/download/iq8m-iq8a-microinverter-data-sheet
If you reference the current Enphase Spec, you will see that the voltage input is limited to 60 volts and the ISC amperage current input is set to 25AMPS. as demonstrated below from the Enphase data sheet. Notice the IQ8-60 series is only allowed to have 50 volts but shares the 25 amp rating.
Enphase PCS
Enphase Directs us to make sure we add the continuous use factor in their trainings.
Lets say you have a 200 amp bus and 200 amp main breaker in your MSP
200 * 1.2 - 200 = 40
40 * .75 or 40/1.25 will give 32 amps which should be the limit of how much we can backfeed on an Enphase PCS System.