This error typically arises when the meter-mounted Backup Initiation Device (BID) is rated lower than the utility service rating. When this happens this triggers an error.
An Example:
If a Utility service on a residence is rated for 225A and a Tesla Backup Switch is being used as a meter mounted Backup Initiation Device. The Tesla BID is only rated for 200A.
Potential Solution:
One way to resolve this error is to adjust the utility service rating in the SolarAPP+ application to align with the rating of the meter-mounted Backup Initiation Device (BID). In this case, since the Tesla Backup Switch is rated for 200 amps, the utility service feed can be updated to 200 amps in the application to ensure consistency and avoid rating mismatches.