Tesla Resources

The Manufacturer Resource Articles document the most common issues and difficulties when entering a particular manufacturer's equipment into SolarAPP+. If you see an issue that is not documented or needs improvement/ changes. Please reach out to [email protected]



How to enter the Tesla Backup Switch or Gateway 2


Designing Arrays  - 

ISC Amperage Inputs -



R559 Error on SolarAPP+


MODULE ISC(13.66) * 1..25 = 17.075 Exceeds limit of MPPT Input of Tesla Inverter.

SolarAPP compares the Isc at a high irradiance factor (125%) in accordance with  [NEC 690.8(A)(1)(a)(1) -> This is sometimes in the industry referred to as the "high irradiance factor".


Suggestions use smaller wattage module 415- 420 series.


13.58 * 1.25 = 16.975


You can use the bonding jumper to get up to 25 amps of Short Circuit ISC Current.

MPPT Parallel Bonding Jumper


https://help.solar-app.org/article/210-inverter-isc-dc-input-ratings


Contractor Resources:

Powerwall 3 Datasheet

Powerwall 3 Quick Installation Manual

Powerwall 3 Parallel Bonding Jumper Installation

Tesla Powerwall+ Installation

TESLA MCI (Rapid Shutdown) Installation Manual

MPPT Parallel Bonding Jumper

Tesla MCI 2 SPEC

Tesla One Support


MCI HAZARD CONTROL SYSTEM CERTIFICATION

ZS PVHCS datasheet

MCI Design Locations

Important Tesla Model #'s

Powerwall 3 1707000-xx-y
Tesla Backup Gateway 2 1232100-xx-y
Tesla Backup Switch 1624171-xx-y
Powerwall 2 1092170-xx-y or 2012170-xx-y
Powerwall + 1850000-xx-y
3.8kw Inverter 1534000-xx-y
7.68 kW Inverter 1538000-xx-y
11.5 kW Inverter 1707000-xx-y

PCS Features for Tesla Solar Inverter

Powerwall 3 System Design Guide

Tesla Installer Academy Youtube

Powerwall 3 Device Setup and Troubleshooting

Site Limit Feature

Important Notes on UL 1741 PCS Compliance